Relative Humidity - Sensor Element:

Capacitive Polymer with CMOS processes

Relative Humidity - Measurement Range:

0~100%RH

Relative Humidity - Signal Output:

4~20mA, 0~10VDC or Mod-bus

Relative Humidity - Accuracy:

±2%RH(20℃, 20~80%RH)

±3%RH(20℃, 20~80%RH)

Relative Humidity - Long Term Stability:

±1%RH; typical at 50% RH in five years

Temperature - Temp Sensor:

NTC20k, Pt100 , Pt1000

Temperature - Measurement Range:

0~50℃, 0~100℃, -50~50℃

Range selected by Jumper (0~50℃ as default )

Temperature - Signal Output:

4~20mA , 0~10VDC or Mod-bus

NTC20k, Pt100, Pt1000

Temperature - Accuracy:

±0.3℃ at 25℃ for NTC20k sensor

±0.2℃ at 25℃ for Pt100, Pt1000 sensor

±0.2℃ (0~50℃) With transmitter

Temperature - Long Term Stability:

±0.25℃ per year

Power Supply:

24 VAC/VDC ±10%

Current Output Load:

500 Ohm Max

Working temperature:

Room type: -30℃ ~ +70℃

Duct type: -50℃ ~ +70℃

5% ~ 95% RH without condensation

Certification:

CE (Report No. HA110097)

Housing Material:

Plastic (ABS)

Flame retarded acc. to UL94-V1

Protection Standard:

Room type: IP30

Duct, OSA or Immersion: IP65

Calibration: Factory calibrated

品牌

Honeywell

Model

HT3C21, HT3C2P, HT3C2Q, HT3C2K, HT3C31, HT3C3P, HT3C3Q, HT3C3K, HT3C71, HT3C7P, HT3C7Q, HT3C7K, HT3C81, HT3C8P, HT3C8Q, HT3C8K, HT2C21, HT2C2P, HT2C2Q, HT2C2K, HT2C31, HT2C3P, HT2C3Q, HT2C3K, HT2C71, HT2C7P, HT2C7Q, HT2C7K, HT2C81, HT2C8P, HT2C8Q, HT2C8K, HD3C21, HD3C2P, HD3C2Q, HD3C2K, HD3C31, HD3C3P, HD3C3Q, HD3C3K, HD3C71, HD3C7P, HD3C7Q, HD3C7K, HD3C81, HD3C8P, HD3C8Q, HD3C8K, HD2C21, HD2C2P, HD2C2Q, HD2C2K, HD2C31, HD2C3P, HD2C3Q, HD2C3K, HD2C71, HD2C7P, HD2C7Q, HD2C7K, HD2C81, HD2C8P, HD2C8Q, HD2C8K